White Rodgers 50a50 Manual

I recently fixed a White-Rodgers Model 50A51-242 furnace control module that had a problem with one of the blower control relays. This problem turned out to be so easy to fix that I figured I might as well do a write-up on it. Standard bidding at bridge with sayc pdf to excel template.

In my particular case the “HEAT HI” relay was not activating when it should. (For a description of the troubleshooting involved, please see my post on York Deluxe Diamond 80 Furnace repair) Torrent pragmata pro v1.

View and Download White Rodgers 50A55-474 instruction manual online. Welcome to ManualMachine. You have been successfully registered. We have emailed you a verification link to to complete your registration. Please check your inbox, and if you can’t find it. Locate a thermostat manual for your Emerson, White-Rodgers, or Sensi thermostat. Sensi™ Touch Smart Thermostat (White) 1F95U-42WF. Product Information.

Removing the bottom cover

White Rodgers 50a50 241 Manual

I used a 1 inch putty knife and screwdriver to remove the bottom cover. Be careful not to push them in too far which could damage the circuit board.

Upon opening I was very happy to see that there were 3 identical blower control relays on the board: one for low heat (“HEAT LO”), one for high heat (“HEAT HI”), and one for a/c (“COOL”). This was good news because it meant I had a spare relay, as we were not using the a/c function. I would be able to use the a/c relay to replace the high heat relay if need be.

Cold solder joint for “HEAT HI” relay

Stephen’s first real experience in a security company was so traumatic that he left for a few years to work somewhere completely different. However the pull of security was too much and he started cleaning infected websites in his spare time before joining Defiant full-time as a senior developer. Apr 05, 2019 Defiant Lock Company Home Page Rating: 5,6/10 9040 reviews Kwikset is an American lock and lockset manufacturer owned by Spectrum Brands Hardware and Home Improvement Group (HHI), a Division of Spectrum Brands. Originally Gateway Manufacturing Company, Kwikset founded in California in 1946 by Adolf Schoepe, and Karl Rhinehart. Get free shipping on qualified Defiant Door Lock Combo Packs or Buy Online Pick Up in Store today in the Hardware department. Defiant - Door Lock Combo Packs - Door Locks - The Home Depot Store Finder. Defiant lock company home page.

As it turned out, there was no need to replace the high heat relay. A close inspection of the high heat relay’s solder connections showed a very obvious cold solder joint on one of the coil connections. I resoldered this connection, and the problem was fixed. Resoldering the connection did prove to be a little challenging, however. It just would not take the solder. I believe the problem was some kind of coating on the solder. After I carefully scraped the area with a precision screwdriver, and fed in plenty of flux core solder, it finally took the new solder.

Locations of Overheated Area and Cold Solder Joint

I did notice another problem with the board. There are four resistors connected in parallel to provide current to the thermostat. These resistors had obviously become very hot at some point, discoloring the board and melting their solder connections. This probably happened years ago with an older thermostat that drew too much current. Since the furnace is currently hooked up to a digital thermostat, and they draw very little current, I wasn’t too worried. I decided to resolder the resistors just to be on the safe side, but it was probably unnecessary.

Did you lose a service manual for a White Rodgers Thermostat device? Do you have any other problem with it? You got to the right place. There is White Rodgers thermostat troubleshooting table below. It allows to conduct timely diagnostics of an appliance and remove defects.

White Rodgers 50a50 Manual Instructions

50a50

White Rodgers 1 F 78 thermostat troubleshooting

White Rodgers 50a50-288 Manual

SymptomPossible CauseCorrective Action
No Heat/No Cool/No Fan (common problems)1. Blown fuse or tripped circuit breaker.Replace fuse or reset breaker.
2. Furnace power switch to OFF.Turn switch to ON.
3. Furnace blower compartment door or panel loose or not properly installed.Replace door panel in proper position to engage safety interlock or door switch.
4. Loose connection to thermostat or system.Tighten connections.
No Heat1. Pilot light not lit.Re-light pilot.
2. Furnace Lock-Out Condition. Heat may also be intermittent.Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local HVAC service person for assistance.
3. Heating system requires service or thermostat requires replacement.Diagnostic: Set SYSTEM Switch to HEAT and raise the setpoint above room temperature. Within a few seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a HVAC service person to verify the heating is operating correctly.
No Cool1. Cooling system requires service or thermostat requires replacement.Same as diagnostic for No Heat condition except set the thermostat to COOL and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling.
Heat, Cool or Fan Runs Constantly1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in heat/cool/fan system.
4. FAN Switch set to Fan ON.
Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal block. Try resetting the thermostat as described above. If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat.
Thermostat Setting & Thermostat Thermometer Disagree1. Thermostat thermometer setting requires adjustment.The thermometer can be adjusted +/- 4 degrees. See Temperature Display Adjustment in the Configuration Menu section.
Furnace (Air Conditioner) Cycles Too Fast or Too Slow (narrow or wide temperature swing)1. The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate.Digital thermostats provide precise control and cycle faster than older mechanical models. The system turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like an increased cycle time, choose SL for slow cyde in the Configuration menu, step 6 (heat) or 7 (cool). If an acceptable cycle rate is not achieved, contact a local HVAC service person for additional suggestions.
Forgot Keypad Lockout CodePress the menu button (button will disappear) and hold in for 20 seconds. This unlocks the thermostat.

White Rodgers BNP125 thermostat troubleshooting

ProblemSolution
The thermostat is hot.In normal operating conditions, the thermostat housing can reach nearly 40?C at maximum load. That is normal and will not affect the effective operation of the thermostat.
Heating is always on.Check if the thermostat is properly connected.
Heating does not run even if the thermostat indicates it is on.
The display does not turn on.Check if the thermostat is properly connected.
The display turns off a few minutes and then turns on again.The thermal protection of the heating unit has opened due to overheating. Check if the heating unit is in good condition of operation and that clearance around the appliance is according to the manufacturer’s specifications.
The display has low contrast when heating is on.The load is lower than the minimum load. Install a heating unit that is within the load limits of the thermostat.
The displayed ambient temperature is incorrect.Check the presence of an air stream or a heat source near the thermostat, and correct the situation.
The display indicates E1 or E2.Faulty thermal sensor. Contact the customer service.
Weak luminosity of the display.Possibility of a bad contact. Check thermostat wirings.

White Rodgers P200 thermostat troubleshooting

White Rodgers 50a50 405 Manual

OptionsDefault SettingAdditional Information
Set the temporary Hold Time (HOLD)00:00Select desired time, in 15-minute increments, for the duration of a temporary override of the current temperature. If you are not sure what to chose, 2 hour setting is usually a good starting point.
Do you want the Cycle Rate to be Fast or Slow?FA (fast)Select SL (slow) if you have Hydronic (water or steam) heating. Otherwise, select default FA.
Do you want the display light on (d-L) for a short time after any key is pressed?ONUse default ON to enable backlight
Do you want the Energy Management Recovery(E) function to be enabled?ON (enabled)Select default ON.
Ensures the desired temperature is reached by the designated program schedule time
Do you want to be reminded when it is time to change the air filter? (FLTR)000 (no reminder)Select default 000 for now.
Compressor Lockout (LOC)OFFSelect ON to provide protection to your Heating and Cooling System’s compressor
How much displayed temperature offset do you want?OHI (no offset)Select default OHI for now.
Do you want temperature displayed in ?C (Celsius) or ?F (Fahrenheit)??F (Fahrenheit)